Physico‑chemical assessment of indoor air quality of a tertiary hospital in South–South Nigeria

Main Article Content

K. Emuren
B. Ordinioha

Abstract

 Background: Good ventilation is one of the structural designs used to reduce the risk of transmission of airborne infections in hospitals. This is, however, rarely observed in Nigeria as hospital designs used to shut out the inclement weather in temperate countries are copied without much modification. This study assessed the physico-chemical air quality at different areas of the University of Port Harcourt Teaching Hospital, Port Harcourt, to ascertain the level of pollutants in the ambient air.


Methods: The study was carried out in July, 2015, in randomly selected inpatient wards, outpatient clinics and clinical laboratories of the hospital, using the appropriate measuring equipment. The study tested for the presence of particulate matter 2.5 (PM2.5), volatile organic compounds (VOCs) and nitrogen dioxide (NO2) in the ambient air; as well as the prevailing micrometeorological indices of relative humidity, temperature, wind direction and speed of the study sites.


Results: A total of 36 air quality measurements were carried out in nine study sites in the hospital. The assessed pollutants were present in the ambient air of most of the study sites but were within the regulatory limits. The concentration of NO 2 in the study sites ranged from 133 µg/m3 in the immunisation clinic to 151 µg/m3 in the gynaecology ward, with a mean concentration of 141 µg/m3; while PM2.5 was not detected in the gynaecology and urology wards and present in very low levels in the other study sites. There was, however, greater variability in the levels of VOCs, ranging from 236.57 mg/m3 in the HIV clinic to 530.77 mg/m3 in the male surgical ward.


Conclusion: The levels of the assessed pollutants were within regulatory levels, even as there were evidence of poor ventilation in several of the study sites.

Downloads

Download data is not yet available.

Article Details

How to Cite
Physico‑chemical assessment of indoor air quality of a tertiary hospital in South–South Nigeria. (2016). Port Harcourt Medical Journal, 11(1), 21-25. https://doi.org/10.60787/phmj.v11i1.58
Section
Original Articles

References

1. Murray C, Lopez A. The Global Burden of Disease: A Comprehensive Assessment of Mortality and Disability from Disease, Injuries and

Risk Factors in 1990 and Projected to 2020. Boston, MA: Harvard University Press, 1996.

2. World Health Organization. Current and Future Long‑term Needs. Geneva: World Health Organization, 2002.

3. Adams J, Bartem J, Chartier Y, editors. Essential Environmental Health Standards in Health Care. Geneva: World Health Organization, 2008.

4. Menzies D, Fanning A, Yuan L, FitzGerald JM. Hospital ventilation and risk for tuberculous infection in Canadian health care workers.

Canadian Collaborative Group in Nosocomial Transmission of TB. Ann Intern Med 2000;133:779‑89.

5. Atkinson J, Chartier Y, Pessoa‑Silva CL, Jensen P, Li Y, Seto WH. Natural ventilation for infection control in health‑care settings. Geneva:

World Health Organization, 2009.

6. Brandt‑Rauf PW, Andrews LR, Schwarz‑Miller J. Sick‑hospital syndrome. J Occup Med 1991;33:737‑9.

7. Ordinioha B, Sawyer W. The environmental health condition of the new University of Port Harcourt Teaching Hospital. Niger Health J

2012;11:117‑9.

8. World Health Organization. WHO Air Quality Guidelines for Particulate Matter, Ozone, Nitrogen Dioxide and Sulfur Dioxide:Global Update 2005, Summary of Risk Assessment. Geneva: World Health Organization, 2006.

9. El‑Sharkawy MF, Noweir ME. Indoor air quality levels in a university hospital in the eastern province of Saudi Arabia. J Family Community Med 2014;21:39‑47.

10. ASHRAE, ANSI/ASHRAE Standard 62‑2001. Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating,

Refrigerating and Air‑Conditioning Engineers, Inc., 2001.

11. Gouveia N, Fletcher T. Time series analysis of air pollution and mortality: Effects by cause, age and socioeconomic status. J Epidemiol

Community Health 2000;54:750‑5.

12. World Health Organization. Air Quality Guidelines for Europe. 2nd ed. WHO Regional Publications, European Series No. 91. Copenhagen: World Health Organization, 2000.

13. Leung M, Chan AH. Control and management of hospital indoor air quality. Med Sci Monit 2006;12:SR17‑23.

14. Jung C, Wu P, Su H. Indoor air quality varies with ventilation types and working areas in hospitals. Build Environ 2015;85:190‑5.

15. Bessonneau V, Mosqueron L, Berrubé A, Mukensturm G, Buffet‑Bataillon S, Gangneux JP, et al. VOC contamination in hospital,

from stationary sampling of a large panel of compounds, in view of healthcare workers and patients exposure assessment. PLoS One

2013;8:e55535.

16. Takigawa T, Horike T, Ohashi Y, Kataoka H, Wang DH, Kira S. Were volatile organic compounds the inducing factors for subjective

symptoms of employees working in newly constructed hospitals? Environ Toxicol 2004;19:280‑90.

17. US EPA. An Introduction to Indoor Air Quality: Volatile Organic Compounds (VOCs). Washington, DC: US Environmental Protection

Agency; 2012b. Available from: http://www.epa.gov/iaq/voc.html. [Last accessed on 2015 Jun 07].

18. Yousef BA, Elshareef AA, Ibraheem MA, Alsayed SS. Assessment of Indoor air quality in medical facilities in Sudan. Int J Sci Technol Res

2013;2:92‑5.

19. Reddy S. Latex allergy. Am Fam Physician 1998;57:93‑102.

Similar Articles

You may also start an advanced similarity search for this article.